K-factor isolation transformer

PRODUCT

CONTACT US

Tel:400-685-8582

Tel:+86-21-57715555
          +86-21-37831986

Fax:+86-21-37831846

Phone:13817716438

Email:weho@chinaweho. com

Address:Building 2, No.8 Nanle Road, Songjiang District, Shanghai

K13 coefficient isolation transformer

K13 coefficient isolation transformer K13 coefficient isolation transformer

K13 coefficient isolation transformer

  • Category:K-factor isolation transformer
  • K-factor isolation transformer product overview: Weihao K-factor safety isolation transformer is produced by Dongwen Transformer Co., Ltd. using high-quality materials and advanced technology for many years. It has the advantages of moisture-proof,
  • Hotline:021-57715555   13817716438
Product Description

K-factor isolation transformer product overview:

Weihao K-factor safety isolation transformer is produced by Dongwen Transformer Co., Ltd. using high-quality materials and advanced technology for many years. It has the advantages of moisture-proof, convenient maintenance, etc. It can penetrate deep into the load center and can be used for import and export equipment, professionally supporting subways, airports, high-rise buildings, stations, wharves, enterprises and tunnels and other power transmission and distribution places. The K13 coefficient is a general special measure of the harmonic heating effect, especially for the harmonics on the transformer. It not only emphasizes the harmonic frequency, but also emphasizes the harmonic order, harmonic spectrum distribution and spectrum ratio. The K-factor isolation transformer is mainly used for When a large amount of nonlinear load is required. Designed according to the American UL1561 standard, there are K4, K9, K13, K20, K30, K40, K50 and other coefficients. K-13 is a common load for office loads and general computer room loads, K-20 tends to be dedicated computer loads (precision air conditioners and precision motors) and power quality sensitive equipment PDUs (power distribution units). The K coefficient isolation transformer is mainly used in various power supply places with AC 50-60Hz and voltage not exceeding 3300V, and the distribution of various input and output voltages, connection groups, and tap line group capacity of products can be carefully designed according to user requirements. with manufacturing.

Main parameters of K coefficient isolation transformer products;


Rated capacity: 30KVA-500KVA

Input voltage: three-phase 400v 380v

Output voltage: three-phase 400V 380v

Voltage fluctuation rate: ±1%

Output waveform distortion: no distortion (compared to input waveform)

Insulation class: F class, H class (regularly H class) temperature resistance 180°

Work efficiency: ≥98%

Applicable frequency: 50/60Hz

Connection method: DYN11

Overload capacity: Allow more than 1.5 times the rated load to work for 1 hour (long-term full load)

Noise: ≤35dB (within one meter)

Temperature rise: ≤60K

Insulation resistance: ≥150MΩ

Dielectric strength: 3000VAC/1min

Design life: 22 years

Working environment: Temperature: -20~+50℃ Humidity: ≤95%RH without condensation

Workplace: No corrosive gas and conductive dust

Safety standard: the product conforms to VDE0550, IEC439, JB5555, GB226 and other international national standards

Cooling method: dry air cooling

K-factor isolation transformer application range;

Used in major media TV power supply centers, office computer rooms, machinery facilities, large-scale electromechanical equipment, metal processing equipment, production lines, construction engineering equipment, elevators, transportation, post and telecommunications, military, railway, import and export equipment, scientific research and culture Medical equipment, embroidery and textile equipment, air conditioners, radio and television, household appliances, lighting and other places that require voltage transformation.