Address:Building 2, No.8 Nanle Road, Songjiang District, Shanghai

Indoor high pressure compressed air load switch FKRN12

Indoor high pressure compressed air load switch FKRN12 Indoor high pressure compressed air load switch FKRN12

Indoor high pressure compressed air load switch FKRN12

  • Category:High voltage load switch
  • product description FN12-12D/630-20 indoor AC high-voltage load switch (hereinafter referred to as FN12-12D load switch) is a three-phase high-voltage switchgear with a rated voltage of 12KV and a rated frequency of 50Hz. No-load transformer and ca
  • Hotline:021-57715555   13817716438
Product Description

product description

FN12-12D/630-20 indoor AC high-voltage load switch (hereinafter referred to as FN12-12D load switch) is a three-phase high-voltage switchgear with a rated voltage of 12KV and a rated frequency of 50Hz. No-load transformer and cable charging current, close short-circuit current. The load switch equipped with the grounding switch can withstand short-circuit current.

FN12-12D.R/100-31.5 type indoor AC high voltage load switch - fuse combination (hereinafter referred to as FN12-12D.R combination) is a FN12-12D load switch disconnecting and S LAJ-12 (XRNT ) -12) Indoor high-voltage switchgear combined with high-voltage current-limiting fuses. It can reliably interrupt any current up to the short-circuit current: the load switch interrupts the working current, the fuse interrupts the short-circuit current, and jointly interrupts any overcurrent between the working current and the full short-circuit current, and the fuse through its striker makes The load switch is open.

Model and meaning

See picture on desktop

normal working environment

1. Ambient air temperature: upper limit +40°C, lower limit -25°C.

2. The altitude is 1000m and below.

3. Relative humidity: the monthly average is not more than 90%, and the daily average is not more than 95%.

4. The surrounding air should not be obviously polluted by corrosive or combustible gas and water vapor.

5. No regular strenuous exercise.

6. Anti-pollution grade: Class II.

If the conditions of use exceed the above-mentioned provisions, it shall be determined by the user and the manufacturer through negotiation.

Technical parameters performance

serial number project unit FN12-12D/630-20 FN12-12D.R/100-31.5
1 Rated voltage kV 12
2 Rated frequency Hz 50
3 Rated current A 630 100
4 Lightning impulse withstand voltage kV Ground and interphase 75, isolation 85
5 1min power frequency withstand voltage kV Ground and phase 42, isolation 48
6 Rated thermal stability current kA 20 (4S)
7 Rated dynamic stable current kA 50
8 Rated making current (peak value) kA 50
9 Rated short-circuit breaking current kA 31.5
10 Rated transfer current kA 1.5
11 Maximum breaking current (reference value) kA 1.8
12 Breaking no-load transformer capacity Kva 1250
13 Rated cable charging current A 10
14 Rated active load current breaking times Second-rate >100
15 The impactor triggers the load switch opening time S >0.06
16 Grounding switch thermally stable current kA 20 (2S) 20 (2S)
17 Grounding switch thermally stable current (peak) kA 50 50
18 Motor operating supply voltage V AC220, DC48

Mechanical characteristic parameters

serial number project unit FN12-12D/630-20 FN12-12D.R/100-31.5
1 Auxiliary contact distance mm >155
2 Three-phase opening and closing synchronization ms <3
3 just point speed m/s >2.8 2.80+0.4
4 just closing speed m/s >3.8
5 Grounding switch fracture distance mm 145±5
6 Main circuit resistance μΩ <120 <300
7 maximum operating force Nm <160 <180

The main technical parameters

serial number model Fusing rated current (A) Equipped with transformer capacity (kVA)
UK model GB model
1 SDLAJ-12 XPNT□-12 16 100, 125, 160
2 20 200
3 25 250
4 31.5 315
5 40 400
6 SFLAJ-12 50 500
7 63 630,800
8 80 1000
9 SSLAJ-12 100 1250
10 SKLAJ-12 125 1600