PRODUCT
Tel:400-685-8582
Tel:+86-21-57715555
+86-21-37831986
Fax:+86-21-37831846
Phone:13817716438
Email:weho@chinaweho. com
Address:Building 2, No.8 Nanle Road, Songjiang District, Shanghai
Transformer for export equipment
- Category:Isolation transformer for export equipment
- product description SG-F series imported equipment supporting three-phase dry-type isolation transformer is a new generation of energy-saving power transformer developed and produced by our factory on the basis of referring to similar internationa
- Hotline:021-57715555 13817716438
product description
SG-F series imported equipment supporting three-phase dry-type isolation transformer is a new generation of energy-saving power transformer developed and produced by our factory on the basis of referring to similar international products and combining my country's national conditions. , National standard, the winding adopts the method of unwrapped and whole-column winding; the transformer is vacuum dipped, so that the insulation level of the transformer reaches F or H level, and the product performance reaches the advanced level at home and abroad. SG-F series three-phase dry-type isolation transformers are widely used in circuits with AC 50Hz to 60Hz and voltage below 3300V. Wait. The various input and output voltage levels of the product, the connection group, the number and position of the adjustment taps (generally ±5%), the distribution of the winding capacity, the configuration of the secondary single-phase winding, the use of the rectifier circuit, whether the belt is required Shells, etc., can be carefully designed and manufactured according to user requirements.
Features
Establishing a new neutral line-grounding in the isolation transformer can relieve the common mode interference of the power grid and the troubles of other neutral lines. The isolation transformer converts the three-wire △ connection into a four-wire Yo system, and the shielding further eliminates the high-frequency pulse interference coupled by the transformer. Although the shielded isolation transformer can effectively prevent interference from various NGs (pulse and high-frequency noise), the transformer must be properly grounded and very strict, otherwise the anti-common mode interference will be ineffective. The company can design and produce high-quality isolation transformers for customers.
Features advantages:
ØHigh isolation
ØN-G has good performance
ØHigh common mode interference rejection
Ø Convert △ to Y or Y to △
Ø Voltage taps are easy to change
ØDesigned according to the special performance requirements of users
Technical indicators
1. Input rated voltage: three-phase 380V or single-phase 380V or single-phase 220V
2. Output rated voltage: three-phase 220V/200V/208V/230V/480V or single-phase 110V/120V/127V/
3. Working frequency: 50Hz-60Hz
4. Efficiency: ≥95%
5. Temperature rise: <60K
6. Waveform distortion: <0.1%
7. High voltage test: 2500V, no breakdown for 1 minute
8. Insulation resistance: winding to ground insulation resistance ≥ 500M ohms, primary to secondary insulation resistance ≥ 500M ohms
Shape and installation dimensions
model | Capacity (KVA) | Output voltage (V) | join group number | Dimensions (mm) | ||||||
enter | output | account opening | protective | |||||||
Bmax | Dmax | Emax | Bmax | Dmax | Dmax | |||||
SG-F-0.15 | 0.15 |
660 380 220 |
380 220 200 127 |
V/V Y/yno(Y/yo) Y/d(Y/) D/Y(△/Y) Y/d(△/△) |
200 | 105 | 140 | 260 | 180 | 160 |
SG-F -0.3 | 0.3 | 180 | 110 | 180 | 260 | 180 | 160 | |||
SG-F -0.5 | 0.5 | 180 | 115 | 180 | 260 | 200 | 120 | |||
SG-F -0.75 | 0.75 | 230 | 130 | 200 | 260 | 250 | 260 | |||
SG-F-1 | 1 | 230 | 140 | 200 | 315 | 200 | 260 | |||
SG-F-1.5 | 1.5 | 230 | 155 | 200 | 355 | 290 | 280 | |||
SG-F-2 | 2 | 270 | 165 | 250 | ||||||
SG-F-2.5 | 2.5 | 270 | 175 | 250 | 370 | 290 | 300 | |||
SG-F-3 | 3 | 270 | 185 | 250 | ||||||
SG-F-4 | 4 | 300 | 180 | 285 | 510 | 400 | 550 | |||
SG-F-5 | 5 | 300 | 200 | 285 | ||||||
SG-F-10 | 10 | 370 | 210 | 240 | 560 | 430 | 600 | |||
SG-F-15 | 15 | 420 | 245 | 390 | 600 | 440 | 620 | |||
SG-F-20 | 20 | 540 | 320 | 450 | 650 | 440 | 650 | |||
SG-F-30 | 30 | 540 | 380 | 480 | 870 | 500 | 780 | |||
SG-F-40 | 40 | 750 | 350 | 520 | 960 | 550 | 810 | |||
SG-F-50 | 50 | |||||||||
SG-F-60 | 60 | 800 | 450 | 650 | 1000 | 810 | 810 | |||
SG-F-80 | 80 | |||||||||
SG-F-100 | 100 | 860 | 450 | 650 | 1050 | 810 | 810 | |||
SG-F-125 | 125 | 860 | 500 | 700 | ||||||
SG-F-160 | 160 | 950 | 600 | 800 | ||||||
SG-F-200 | 200 | 1000 | 680 | 850 | ||||||
SG-F-250 | 250 | 1050 | 700 | 850 |
Conditions of Use
1. Applicable altitude: ≤5000m
2. Ambient temperature: -15℃~+45℃
3. Relative humidity: ≤90%
4. The installation site should be free of gas, steam, chemical deposits, dirt, conductive dust and other explosive, flammable and corrosive substances that seriously affect the insulation strength of the transformer.
5. Those that do not meet the above conditions of use should be negotiated with us.